Comparison of different frequency controllers for a VSC-HVDC supplied system

Författare

Summary, in English

This paper studies three different frequency controllers and their effects on the voltage disturbance ride-through capability of a VSC-HVDC supplied industrial system. The idea of implementing frequency controller is to improve the power quality of industrial plants by slightly decreasing the VSC output voltage frequency since industrial processes are more sensitive to voltage drops than frequency deviations. The first two controllers, frequency controllers I and II, are fixed frequency controllers and the third one, frequency controller III, is a PI frequency controller. In order to compare three different controllers, a system with a simplified VSC-HVDC and different load types is simulated in PSCAD/EMTDC. Simulation results show that with frequency controller III, the VSC-HVDC supplied industrial plant can avoid a voltage collapse by decreasing frequency during or after disturbances. Furthermore, with an increase of the converter current limit, the possibility of mitigating voltage dips increases. For frequency controllers I and II, the extent of the disturbance ride-through capability depends on the current limit of the VSC-UVDC. A higher current limit results in a higher ride-through capability. The effect of the dc capacitor on improving the system voltage disturbance tolerance is also investigated during and after disturbances when the VSC-HVDC uses frequency controller I. The system voltage disturbance ride-through capability increases with an increase of the dc capacitance or the current limit.

Publiceringsår

2008

Språk

Engelska

Sidor

2224-2232

Publikation/Tidskrift/Serie

IEEE Transactions on Power Delivery

Volym

23

Issue

4

Dokumenttyp

Artikel i tidskrift

Förlag

IEEE - Institute of Electrical and Electronics Engineers Inc.

Ämne

  • Other Electrical Engineering, Electronic Engineering, Information Engineering

Nyckelord

  • voltage source converters-high-voltage direct
  • ride-through capability
  • voltage disturbance
  • voltage dips
  • current limit
  • frequency controllers
  • current (VSC-HVDC)

Status

Published

ISBN/ISSN/Övrigt

  • ISSN: 1937-4208