Limitations of Water Mist as a Total Flooding Agent

Författare

  • Petra Andersson
  • Göran Holmstedt

Summary, in English

The limitations of water mist in acting as a total flooding agent are discussed in this paper. The paper focuses on water mist consisting of droplets 1-100 µm in diameter. Water mists are very efficient as an extinguishing media if they are present in the flame. There are, however, several problems associated with introducing the water mist into the flame: the spray reaches only a short distance; small water droplets have a very short lifetime; droplets coagulate into larger droplets; large droplets hit obstacles such as walls and therefore have difficulties in being dispersed throughout the protected volume.

Publiceringsår

1998

Språk

Engelska

Sidor

31-50

Publikation/Tidskrift/Serie

Journal of Fire Protection Engineering

Volym

9

Issue

4

Dokumenttyp

Artikel i tidskrift

Förlag

SAGE Publications

Ämne

  • Building Technologies
  • Other Civil Engineering

Status

Published

ISBN/ISSN/Övrigt

  • ISSN: 1042-3915