Burst detection and location in water distribution networks

Författare:
Publiceringsår: 2005
Språk: Engelska
Sidor: 71-80
Publikation/Tidskrift/Serie: Water Supply
Volym: 5
Nummer: 3-4
Dokumenttyp: Konferensbidrag
Förlag: IWA Publishing

Sammanfattning

An algorithm for the detection and location of sudden bursts in water distribution networks combining both continuous monitoring of pressure and hydraulic transient computation is presented. The approach is designed for medium and large bursts that are the result of the sudden rupture of the pipe wall or other physical element in the network and are accompanied by the transient pressure wave that propagates throughout the network. The burst-induced transient wave arrival times and magnitudes measured at two or more points are used to find the location of a burst. The wave arrival times and magnitudes are detected using the modified cumulative sum (CUSUM) change detection test. Results of validation on a real network show the potential of the proposed burst detection and location technique to be used in water distribution systems.

Disputation

Nyckelord

  • Technology and Engineering
  • Burst detection and location
  • hydraulic transients
  • monitoring
  • pipe networks

Övriga

IWA 3rd Int. Conference on Efficient Use and Management of Water
15-18 March, 2005
Santiago, Chile