Typical Load Shapes for Swedish Schools ans Hotels
Författare
Summary, in English
In this study, typical load shapes for two categories of Swedish commercial and public buildings – schools and hotels – are presented and discussed. The measurements from 13 schools and 9 hotels in the south part of Sweden were analysed. Load shapes are developed for different mean daily outdoor temperatures and different day-types - standard weekdays and standard weekends. The load shapes are presented as non-dimensional normalised 1-hour load. The typical load shapes give a reasonable approximation of the measured load shapes, although the relative errors exceed 20% of the mean values during some hours. Daytime (9 a.m.-5 p.m.) results are generally good with errors about 10%. Absolute errors remain relatively constant during the year but as mean values decrease, the relative errors increase, causing relative errors up to 30% during some time periods.
Publiceringsår
1998
Språk
Engelska
Sidor
145-157
Publikation/Tidskrift/Serie
Energy and Buildings
Volym
28
Fulltext
Dokumenttyp
Artikel i tidskrift
Förlag
Elsevier
Ämne
- Electrical Engineering, Electronic Engineering, Information Engineering
Nyckelord
- Load shapes
- schools
- hotels
- Sweden
Status
Published
ISBN/ISSN/Övrigt
- ISSN: 1872-6178