Behaviour of an Intumescing System Subjected to Different Heating Conditions
Författare
Redaktör
- Stephen Grayson
Summary, in English
The start of expansion reaction in the tested fire stopper was around 180°C. The start of reaction temperature is rather independent of the incident heat flux, while expansion rate is clearly dependent on the incident heat flux. Furthermore, the studied fire stopper performed well in the small-scale furnace because the graphite expanded enough to give the same protection, although it is preheated or wet, as when subjected to a heat exposure similar to ISO 834. These results are good but they are only considered valid for the studied system and for the given situation. Future research is needed in order to study how other types of intumescing fire protection systems work when subjected to realistic fire environments.
Avdelning/ar
Publiceringsår
2013
Språk
Engelska
Sidor
187-196
Publikation/Tidskrift/Serie
Fire and Materials - 13th International Conferance and Exhibition
Fulltext
- Available as PDF - 795 kB
- Download statistics
Dokumenttyp
Konferensbidrag
Förlag
Interscience Communications Ltd
Ämne
- Building Technologies
- Other Civil Engineering
Conference name
Fire and Materials 2013
Conference date
2013-01-28
Conference place
San Francisco, United States
Status
Published
Forskningsgrupp
- Fire dynamics