Meny

Du är här

Islanding detection and connection requirements

Författare:
Publiceringsår: 2007
Språk: Engelska
Sidor: 3239-3244
Publikation/Tidskrift/Serie: 2007 IEEE Power Engineering Society General Meeting, Vol 1-10
Dokumenttyp: Konferensbidrag
Förlag: IEEE Press

Sammanfattning

This paper reflects how anti-islanding protection has developed with increasing DG penetration. Starting from a local issue it has developed to possibly affect system security. The focus here is on how islanding detection methods and anti-islanding protection settings relate to distribution level and TSO requirements. It is confirmed using field measurements and simulations that the most common passive islanding detection methods cannot identify balanced island operation. Active methods can detect a balanced island, but is on the other hand not applicable to all DG units. Altogether it is motivated to reconsider anti-islanding protection taking into account the interests of all involved parties. Doing this reveals that anti-islanding protection based on power fine carrier involving the distribution company may be the solution of the future.

Disputation

Nyckelord

  • Technology and Engineering
  • power system
  • power system generation
  • dispersed storage and generation
  • protection

Övriga

IEEE-Power-Engineering-Society General Meeting