Theoretical and experimental evaluation of a plate heat exchanger aftercooler in an evaporative gas turbine cycle

Författare

Summary, in English

The evaporative gas turbine pilot plant (EvGT) has been in operation at Lund Institute of Technology in Sweden since 1997. This article presents the experimental and theoretical results of the latest process modifications made, i.e. the effect of the installation of an aftercooler. The purpose of the aftercooler is to increase the performance of the cycle by utilizing more low-level heat in the humidification tower. The chosen aftercooler is of plate heat exchanger type, which, is very compact, has high thermal efficiency and low pressure drop. The installation of an aftercooler lowers the temperature of the air entering the humidification tower. This also lowers the temperature of the circulating humidification water, which facilitates the extraction of more low-level heat from the economizer. This low-level heat can be utilized to evaporate more water in the humidification tower and thus increase the gas flow in the expander. The pilot plant has been operated at different loads and the measured results has been evaluated and compared with theoretical models. The performance of a plate heat exchanger in power plant applications has also been evaluated. Experience from the measurements has then been used for the potential cycle calculations. It has been shown that the aftercooler lowers the flue gas temperature in the pilot plant to 93

Avdelning/ar

Publiceringsår

2003

Språk

Engelska

Sidor

103-111

Publikation/Tidskrift/Serie

American Society of Mechanical Engineers, International Gas Turbine Institute, Turbo Expo (Publication) IGTI

Volym

3

Dokumenttyp

Konferensbidrag

Förlag

American Society Of Mechanical Engineers (ASME)

Ämne

  • Energy Engineering

Nyckelord

  • Humidification tower
  • Steam-injected gas turbine (STIG)

Conference name

2003 ASME Turbo Expo

Conference date

2003-06-16 - 2003-06-19

Conference place

Atlanta, GA, United States

Status

Published

ISBN/ISSN/Övrigt

  • CODEN: AMGIE8