Automatic Determination of Parameters in Dynamic Load Models from Normal Operation Data

Författare:
Publiceringsår: 2003
Språk: Engelska
Sidor: 1375-1378
Publikation/Tidskrift/Serie: 2003 IEEE Power Engineering Society General Meeting, vols 1-4, Conference Proceedings
Volym: 3
Dokumenttyp: Konferensbidrag
Förlag: Institute of Electrical and Electronics Engineers Inc.

Sammanfattning

Various parameters in dynamic load models were determined from the normal operation data. Steady state load-voltage dependence, transient load-voltage dependence and a load recovery time constant parameters were chosen for the study. It was observed that large variability in voltage was due to high diversity of load processes. It was also observed that transient reactive load-voltage dependence was associated to the load composition and the prescence of induction motors in it.

Disputation

Nyckelord

  • Technology and Engineering
  • Load-voltage characterstics
  • Load stability
  • Dynamic load modeling