Thermal analysis of plate condensers in presence of flow maldistribution
Författare
Summary, in English
Flow maldistribution in plate heat exchangers causes deterioration of both thermal and hydraulic performance. The situation becomes more complicated for two-phase flows during condensation where uneven distribution of the liquid to the channels reduces heat transfer due to high liquid flooding. The present study evaluates the thermal performance of falling film plate condensers with flow maldistribution from port to channel considering the heat transfer coefficient inside the channels as a function of channel flow rate. A generalized mathematical model has been developed to investigate the effect of maldistribution on the thermal performance as well as the exit quality of vapor. A wide range of parametric study is presented, which shows the effects of the mass flow rate ratio of cold fluid and two-phase fluid, flow configuration, number of channels and correlation for the heat transfer coefficient. The analysis presented here also suggests an improved method for heat transfer data analysis for plate condensers.
Avdelning/ar
Publiceringsår
2006
Språk
Engelska
Sidor
4966-4977
Publikation/Tidskrift/Serie
International Journal of Heat and Mass Transfer
Volym
49
Issue
25-26
Länkar
Dokumenttyp
Artikel i tidskrift
Förlag
Pergamon Press Ltd.
Ämne
- Energy Engineering
Nyckelord
- phase change
- condensation
- transport processes
- heat transfer
- mathematical modelling
Status
Published
ISBN/ISSN/Övrigt
- ISSN: 0017-9310