Impact of hybrid ventilation and sewage heat recovery on the energy performance of a low energy building; a feasibility study

Författare

Summary, in English

A hybrid ventilation system including sewage heat recovery for low energy buildings has been

investigated using TRNSYS. Energy from solar collectors is used in combination with the heat

recovered from the sewage system to preheat the ventilation air and the cold water for domestic

use. Results show that the new system renders a possibility to use natural ventilation in passive

houses and zero energy buildings. The annual auxiliary energy need for the new system is lower

than for a conventional fan driven ventilation systems using air/air heat recovery units. Depending

on technical solution and site of installation, the system can provide free cooling during the

summer. Since the new system mainly runs on natural forces it is also more silent compared to

standard mechanical ventilation systems.

Publiceringsår

2010

Språk

Engelska

Publikation/Tidskrift/Serie

[Host publication title missing]

Dokumenttyp

Konferensbidrag

Förlag

International Solar Energy Society

Ämne

  • Civil Engineering

Conference name

EuroSun 2010

Conference date

2010-09-28 - 2010-10-01

Conference place

Graz, Austria

Status

Published

Forskningsgrupp

  • Energy and Building Design