Webbläsaren som du använder stöds inte av denna webbplats. Alla versioner av Internet Explorer stöds inte längre, av oss eller Microsoft (läs mer här: * https://www.microsoft.com/en-us/microsoft-365/windows/end-of-ie-support).

Var god och använd en modern webbläsare för att ta del av denna webbplats, som t.ex. nyaste versioner av Edge, Chrome, Firefox eller Safari osv.

Energy Simulations for Glazed Office Buildings in Sweden

Författare

Summary, in English

Highly glazed buildings are designed by architects to be airy, light and transparent with more access to daylight. Their energy efficiency, however, has become questioned. Therefore, energy simulations of single skin office buildings in Sweden were carried out, using a dynamic energy simulation tool. In order to study the impact of glass on the energy use during the occupation stage, office building alternatives with 30, 60 and 100% window to external wall area were studied. Other varied parameters were the building's orientation, the plan type (open and cell plan offices), the control set points and the façade elements (type and size of windows, type and position of shading devices, etc.). The main conclusion is that careful design is needed to ensure low energy use and good thermal comfort, especially for highly glazed office buildings. Careful design of glazed office buildings has to be based on detailed thermal simulations. Especially in fully glazed buildings (in which the façade is more “sensitive” to climatic conditions), proper combination of control set points, glazing and solar shading are crucial for the energy performance.



A sensitivity analysis of single skin glazed office buildings was one of the main aims of the study. Although it was concluded that highly glazed single skin buildings are likely to consume more energy during the occupation stage, after studying the impact of shadings, window types, etc., the increase was lowered to 15% (100% glazed alternative compared to a typical reference building with 30% window to external wall area) maintaining at the same time an acceptable level of thermal comfort.

Publiceringsår

2008

Språk

Engelska

Sidor

1161-1170

Publikation/Tidskrift/Serie

Energy and Buildings

Volym

Volume 40

Issue

Issue 7

Dokumenttyp

Artikel i tidskrift

Förlag

Elsevier

Ämne

  • Building Technologies

Nyckelord

  • Glazed office buildings
  • Energy simulations
  • Energy use

Status

Published

ISBN/ISSN/Övrigt

  • ISSN: 1872-6178