Fallstudier – Vilka tekniska faktorer spelar en roll vid anlagd brand i skolor?

Författare

Summary, in English

Almost every day a school fire occurs in Sweden. In most cases arson is the cause of the fire. The losses for

these arson fires are considerable. In this report a number of cases studies have been conducted on school

fires in Sweden. The project envisages obtaining more knowledge on the technical factors that influence

the spread of fires with arson in schools. Solutions to mitigate the fire spread in these cases are also

proposed. As methods we used case studies on almost 60 fires, a specific case study in one town and an

enquiry to all fire investigators in the network of MSB. The study resulted in the identification of a

number of technical deficiency and solution to these. Some of the deficiencies are lack of detection systems

and automatic alarm systems, bad construction of roof and voids and insufficient fire barriers. Solutions

for these deficiencies can be automatic alarm systems with efficient location of different type of detectors

(smoke and heat detector cables), good illumination, surveillance cameras and sprinklers. In these areas it

will be necessary to conduct a cost-benefit analysis. The areas which need innovations are fire protection

system for roof eaves nearby the connection between facades and roofs, sprinklers and rescues tactics for

voids. Three possible fire scenarios were identified as important: one outside fire with waste nearby the

façade and two fires inside, with debris inside the school facilities and arson fire by throwing in flammable

liquids. These scenarios are important for the further development of technical solutions. Even that this

study focused on technical requirements a number of organisational deficiencies became apparent. The

systematic fire protection work as described in Sweden (SBA) does not always work as well as it should.

Moreover it is important to create a good environment around the schools which is not the case now in

many locations. Also involvement of school personnel is important. Finally it is important that one needs

to adapt almost a “zero tolerance” towards arson in schools by acting to each incident whether it is small

or large

Publiceringsår

2010

Språk

Svenska

Publikation/Tidskrift/Serie

LUTVDG/TVBB--3148-SE

Dokumenttyp

Rapport

Förlag

Department of Fire Safety Engineering and Systems Safety, Lund University

Ämne

  • Building Technologies
  • Other Civil Engineering

Nyckelord

  • School fires
  • arson
  • case studies
  • technical systems

Status

Published

Report number

3148

Forskningsgrupp

  • Fire dynamics

ISBN/ISSN/Övrigt

  • ISSN: 1402-3504